Permit Number: T11CM02570
Parcel: 13401002D

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T11CM02570
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2011 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Denied NEED COMMUNICATIONS INFO SHEET
08/17/2011 DAVE MANN FIRE REVIEW Approved
08/17/2011 MICHAEL WYNEKEN PLANNING-CITY HALL REVIEW Passed
08/29/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. At detail H/C-4, the structural calculations (page 2) call for 8#5 rebars @ 8" o.c. (?) and the detail calls for #4s @ 12" o.c. Please recalculate and reconcile.
2. Sheet SP-1, Specifications, note 1.13, E calls for 4,000 psi concrete. The structural calculations call for 2,500 psi concrete. Please reconcile.
3. Provide for epoxy anchor special inspection certification as per sheet 6 of the structural calculations.
4. Sheet C-3, Section "A" provides a vertical reinforcing note pointing to horizontal reinforcing. Please correct arrow reference to vertical reinforcing.
5. Please provide structural calculations for the building slab abd turn down footing.
END OF REVIEW
09/12/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2011 SUE REEVES OUT TO CUSTOMER Completed