Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T11CM02570
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/16/2011 | BRIAN HEFFERNAN | COMMUNICATIONS | REVIEW | Denied | NEED COMMUNICATIONS INFO SHEET |
| 08/17/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/17/2011 | MICHAEL WYNEKEN | PLANNING-CITY HALL | REVIEW | Passed | |
| 08/29/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. At detail H/C-4, the structural calculations (page 2) call for 8#5 rebars @ 8" o.c. (?) and the detail calls for #4s @ 12" o.c. Please recalculate and reconcile. 2. Sheet SP-1, Specifications, note 1.13, E calls for 4,000 psi concrete. The structural calculations call for 2,500 psi concrete. Please reconcile. 3. Provide for epoxy anchor special inspection certification as per sheet 6 of the structural calculations. 4. Sheet C-3, Section "A" provides a vertical reinforcing note pointing to horizontal reinforcing. Please correct arrow reference to vertical reinforcing. 5. Please provide structural calculations for the building slab abd turn down footing. END OF REVIEW |
| 09/12/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/15/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |