Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02564
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/25/2011 | BILL BALAK | ZONING | REVIEW | Approved | |
09/13/2011 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/13/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Where are electrical plans for new walk-in cooler. Show circuitry, wire size, conduit sizes, panel location, etc. I am under the impression that Panel B is a new panel therefore all loads are new and you need to show which existing panel feeds it. Where is the oven noted in panel B? |
09/13/2011 | LHANLY1 | WATER | REVIEW | Denied | see comments for plumbing review |
09/13/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 4' is maximum width for egress gate off west patio (IBC chapter 10) Occupancy load calculations missing for pool room and incorrectly calculated for main bar area. Is there an actual chair count available for the bar? And what is size of pool room? |
09/13/2011 | LHANLY1 | WWM | REVIEW | Needs Review | |
09/13/2011 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify if there are any sinks at serving bar. If there are sinks or water supplies then you must provide complete plans |
09/21/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: See IFC 1004. The occupant load was only calculated on partial floor areas in the bar area and pool area. Provide calculations for full area or a seating chart for approval by the Building Official.The only separation appears to be glass. The corridor between the existing bar and the area that used to be market now needs to be fire rated. See IFC Section 1017. The West patio is covered seating and must be counted in the area. 4' is maximum width for egress gate off west patio (IFC Section 1008) Show step heights and locations. See IFC 1008.1.4; if the exit does not comply it must be assumed the legal exit is back though the bar. |
09/22/2011 | SREEVES1 | ADA | REVIEW | Passed | |
12/14/2011 | SREEVES1 | ENGINEERING | REVIEW | Needs Review | |
12/14/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/18/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
06/18/2012 | CINDY AGUILAR | REJECT SHELF | Completed |