Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM02564
Parcel: 12507172A

Address:
2501 E 6TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02564
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2011 BILL BALAK ZONING REVIEW Approved
09/13/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
09/13/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied Where are electrical plans for new walk-in cooler. Show circuitry, wire size, conduit sizes, panel location, etc.

I am under the impression that Panel B is a new panel therefore all loads are new and you need to show which existing panel feeds it.

Where is the oven noted in panel B?
09/13/2011 LHANLY1 WATER REVIEW Denied see comments for plumbing review
09/13/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 4' is maximum width for egress gate off west patio (IBC chapter 10)

Occupancy load calculations missing for pool room and incorrectly calculated for main bar area. Is there an actual chair count available for the bar? And what is size of pool room?
09/13/2011 LHANLY1 WWM REVIEW Needs Review
09/13/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Denied Clarify if there are any sinks at serving bar. If there are sinks or water supplies then you must provide complete plans
09/21/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

See IFC 1004. The occupant load was only calculated on partial floor areas in the bar area and pool area. Provide calculations for full area or a seating chart for approval by the Building Official.The only separation appears to be glass.

The corridor between the existing bar and the area that used to be market now needs to be fire rated. See IFC Section 1017.

The West patio is covered seating and must be counted in the area. 4' is maximum width for egress gate off west patio (IFC Section 1008) Show step heights and locations. See IFC 1008.1.4; if the exit does not comply it must be assumed the legal exit is back though the bar.
09/22/2011 SREEVES1 ADA REVIEW Passed
12/14/2011 SREEVES1 ENGINEERING REVIEW Needs Review
12/14/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/18/2012 CINDY AGUILAR OUT TO CUSTOMER Completed
06/18/2012 CINDY AGUILAR REJECT SHELF Completed