Permit Number: T11CM02560
Parcel: 13216600A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02560
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied RESPONSE TO ORIGINAL COMMENT #6 INCOMPLETE

"CLARIFY LAYOUT OF OF THE FIX-V BRACKETS TO MATCH THE 9 PANEL MODULE RACKS. SHOW THAT # OF BRACKETS REQUIRED FOR EACH MODULE CAN ACTUALLY BE INSTALLED...CONCERN BEING THAT THE WIDER RIBS ON THIS ROOF DECK MAY NOT ALLOW FOR THE CORRECT # OF BRACKETS TO BE INSTALLED."

NO INFORMATION HAS BEEN PROVIDED ON PLANS TO INDICATE WHICH "V" PAGE APPLIES TO ANY PARTICULAR 9 MODULE RACK.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/19/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
10/19/2011 SUE REEVES REJECT SHELF Completed