Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM02560
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM02560
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2011 DAVE MANN FIRE REVIEW Approved
08/22/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/22/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied IBC 106

PLEASE COORDINATE ALL PLANS

1) WHAT IS PURPOSE OF PROVIDING TOPSC #1 LAYOUT AS THIS IS NOT PART OF THIS ACTIVITY (PP S0.3-S1.6)

2) PLEASE CORRECT THE LINE WEIGHT PP S1.8 TO MATCH OTHER SHEETS

3) COORDINATE PANEL ARRAYS BETWEEN A SHEETS AND S SHEETS (USE SAME ARRAY TAGS A,B, ETC.)

4) ENGINEER OF RECORD NEEDS TO REVIEW THE SCHLETTER STRUCTURAL PLANS (IBC 106.3.4.1). VERIFY THAT REQUIRED POINT LOADS HAVE BEEN ADDRESSED FOR THIS ROOF.

5) ENGINEERING DOCUMENTS FROM CORONADO INDICATE THE DETAILED SCHLETTER FIX-V BRACKETS WILL NOT WORK ON THIS ROOF. (2" BRACKET TO BE FIXED TO 5" RIB)

6) CLARIFY LAYOUT OF OF THE FIX-V BRACKETS TO MATCH THE 9 PANEL MODULE RACKS. SHOW THAT # OF BRACKETS REQUIRED FOR EACH MODULE CAN ACTUALLY BE INSTALLED...CONCERN BEING THAT THE WIDER RIBS ON THIS ROOF DECK MAY NOT ALLOW FOR THE CORRECT # OF BRACKETS TO BE INSTALLED.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2011 CPIERCE1 OUT TO CUSTOMER Completed
09/15/2011 SUE REEVES REJECT SHELF Completed