Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T11CM02560
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/22/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | IBC 106 PLEASE COORDINATE ALL PLANS 1) WHAT IS PURPOSE OF PROVIDING TOPSC #1 LAYOUT AS THIS IS NOT PART OF THIS ACTIVITY (PP S0.3-S1.6) 2) PLEASE CORRECT THE LINE WEIGHT PP S1.8 TO MATCH OTHER SHEETS 3) COORDINATE PANEL ARRAYS BETWEEN A SHEETS AND S SHEETS (USE SAME ARRAY TAGS A,B, ETC.) 4) ENGINEER OF RECORD NEEDS TO REVIEW THE SCHLETTER STRUCTURAL PLANS (IBC 106.3.4.1). VERIFY THAT REQUIRED POINT LOADS HAVE BEEN ADDRESSED FOR THIS ROOF. 5) ENGINEERING DOCUMENTS FROM CORONADO INDICATE THE DETAILED SCHLETTER FIX-V BRACKETS WILL NOT WORK ON THIS ROOF. (2" BRACKET TO BE FIXED TO 5" RIB) 6) CLARIFY LAYOUT OF OF THE FIX-V BRACKETS TO MATCH THE 9 PANEL MODULE RACKS. SHOW THAT # OF BRACKETS REQUIRED FOR EACH MODULE CAN ACTUALLY BE INSTALLED...CONCERN BEING THAT THE WIDER RIBS ON THIS ROOF DECK MAY NOT ALLOW FOR THE CORRECT # OF BRACKETS TO BE INSTALLED. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/15/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/15/2011 | SUE REEVES | REJECT SHELF | Completed |