Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T11CM02518
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide unistrut load calculations for the 8' and 12' spans shown on sheet D-1 and in the structural calculations. 2. Please up date the included Table 1609.6.2.1 (2) of the calculations to the 2006 IBC. 3. The standard for minimum lettering size on all drawings is 3/32" uper and lower case. Please correct all lettering on all sheets that are not compliant with this standard and resubmit. 4. The generic framing design at detail 7/D-1 is not even close to the actual panel layout design shown on sheet A-1.0 and is confusing. a. Please delete all generic design layouts and provide a framing design that is as per the panel design layout shown on Sheet A-1.0 and as per the structural calculation key plan. END OF REVIEW |
| 09/07/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/15/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |