Permit Number: T11CM02518
Parcel: 129041830

Review Status: Completed

Review Details: OTHER

Permit Number - T11CM02518
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide unistrut load calculations for the 8' and 12' spans shown on sheet D-1 and in the structural calculations.
2. Please up date the included Table 1609.6.2.1 (2) of the calculations to the 2006 IBC.
3. The standard for minimum lettering size on all drawings is 3/32" uper and lower case. Please correct all lettering on all sheets that are not compliant with this standard and resubmit.
4. The generic framing design at detail 7/D-1 is not even close to the actual panel layout design shown on sheet A-1.0 and is confusing.
a. Please delete all generic design layouts and provide a framing design that is as per the panel design layout shown on Sheet A-1.0 and as per the structural calculation key plan.
END OF REVIEW
09/07/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2011 CPIERCE1 OUT TO CUSTOMER Completed