Permit Number: T11CM02518
Parcel: 129041830

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM02518
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2011 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
08/11/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11cm02518
2000 E Broadway

1. 2005 NEC.690.64(B).2, requires the conductor between over current devices to have the same ampacity as the overcurrent devices added together ?
2. 2005 NEC 690.47(C), requires the grounding electrode conductor between the new 125 a combiner to the solar panels to be no smaller than # 8 ?


Ray Majuta
Elect Pln Ck
PDSD, C of Tuc
8/11/11

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2011 CINDY AGUILAR OUT TO CUSTOMER Completed