Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T11CM02518
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2011 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/11/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11cm02518 2000 E Broadway 1. 2005 NEC.690.64(B).2, requires the conductor between over current devices to have the same ampacity as the overcurrent devices added together ? 2. 2005 NEC 690.47(C), requires the grounding electrode conductor between the new 125 a combiner to the solar panels to be no smaller than # 8 ? Ray Majuta Elect Pln Ck PDSD, C of Tuc 8/11/11 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/11/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |