Permit Number: T11CM02514
Parcel: 12112072A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02514
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PLEASE REFERENCE NEC 690.64 FOR FOLLOWING COMMENTS.

1) MAIN SERVICE BUS IS TOO SMALL FOR APPLIED LOADS. THE 120% ALLOWANCE IN THE EXCEPTION TO 690.64(B)(2) IS ONLY FOR A DWELLING UNIT

2) CONDUCTOR AND DISCONNECTS BETWEEN INVERTER AN MAIN SERVICE TOO SMALL. INVERTER OUTPUT IS LISTED AS 47.5 AMPS. ADD THIS TO THE 60A BREAKER AT THE PANEL AND YOU HAVE 107.5 AMPS AVAILABLE ON THIS EQUIPMENT.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2011 SUE REEVES OUT TO CUSTOMER Completed
08/23/2011 SUE REEVES REJECT SHELF Completed