Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02513
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/16/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PLEASE REFERENCE NEC 690.64 FOR FOLLOWING COMMENTS. 1) MAIN SERVICE BUS IS TOO SMALL FOR APPLIED LOADS. THE 120% ALLOWANCE IN THE EXCEPTION TO 690.64(B)(2) IS ONLY FOR A DWELLING UNIT 2) CONDUCTOR AND DISCONNECTS BETWEEN INVERTER AN MAIN SERVICE TOO SMALL. INVERTER OUTPUT IS LISTED AS 47.5 AMPS. ADD THIS TO THE 60A BREAKER AT THE PANEL AND YOU HAVE 107.5 AMPS AVAILABLE ON THIS EQUIPMENT. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/23/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 08/23/2011 | SUE REEVES | REJECT SHELF | Completed |