Permit Number: T11CM02497
Parcel: 107060380

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02497
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Second request: revise the font size used on the drawings to a minimum of 3/32-inch high (see sheet P1.1). Reference: Section 106.1.1, IBC 2006.
2. Comment not resolved; a 2" cleanout is not approved for use with a 3" drain pipe. [Original comment: Show the size of the under-floor portion of the vents for the floor sinks located in the equipment room and in the sales floor area. The size of that portion of the vent shall comply with the cleanout size requirements of Table 7-6, UPC 2006. Reference: Section 707.11, UPC 2006.]
3. Comment not resolved; the waste and vent schematic shows a mop sink and a floor drain without flow control devices. [Original comment: Each fixture that is connected to a hydromechanical grease interceptor requires a flow control device unless the grease interceptor is equipped with an integral flow control device. Reference: Section 1014.2.1, UPC 2006.]
12/05/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need Approved Site Plan.
2. Need County Health Department activity number.
SHEET NUMBERS A9.4 AND S4.1
3. Detail numbers 1/A9.4 and 108/S4.1 are the same detail but are contradictory to each other. Please reconcile.
END OF REVIEW
12/14/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/15/2011 GERRY KOZIOL WWM REVIEW Denied 4" connection to 8" public sewer per C3.1- need PCRWRD review approval - Chad Amateau 740-6547.
need 3rd floor PCRWRD capaciity evaluation - Kurt Stemm 740-6607.
need WW 5th fl credit evaluation for bldg demo 740-6602 or 740-6606
12/20/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 1395 W. Miracle Mile
T11CM02497 & T11BU03206
Building Plan (2nd Review)

TRANSMITTAL DATE: December 20, 2011

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building and fuel canopy plan and it appears that the plans are consistant with the approved site plan.

3. Due to the amount of comments by other PDSD agencies on the building plan Zoning will stamp and approve the building and fuel canopy plans on the next submittal as long as all other PDSD agencies can approve.

4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956