Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02484
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/09/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the scope of work; if new walls are being installed , will any modifications be made to the mechanical systems. |
| 08/09/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | How can it be determined that existing circuit being added on to is not a dedicated circuit ? Ray Majuta Elect Pln Ck 8/9/11 |
| 08/09/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/09/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a plumbing design for the new point-of-use water dispenser. |
| 08/10/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 08/10/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A2.1: PROVIDE STRUCTURAL CALCULATIONS, NOTES AND DETAILS FOR THE NEW CANOPY. |
| 08/10/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 08/10/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/10/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/19/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |