Permit Number: T11CM02478
Parcel: 10408093B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02478
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2011 MARTIN BROWN FIRE REVIEW Approved
10/19/2011 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Infiniti of Tucson - Expansion
T11CM02478
Site Plan (2nd Review)

TRANSMITTAL DATE: October 19, 2011

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the site plan has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\bldg\t11cm02478.doc
10/21/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/02/2011 ROBERT SHERRY WATER REVIEW Approved
11/02/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/02/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/02/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved. The duct smoke detectors are specified on sheet E0.01 but the note on that sheet says that the duct smoke detector locations are "shown on mechanical plans." [Original comment: Show the locations for the smoke detectors in the return air ducts of heat pumps HP-3 and HP-4, upstream of any outside air connections. Reference: Section 606.1, IMC 2006.]
2. Comment not resolved; no new envelope compliance calculations have been submitted. [Original comment: Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. The building appears to have doors and three different wall types that are not included in the calculations, the roof is not shown as having any cavity-insulation, and the three window types that are included in the calculations are not identified on the drawings. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.]
3. Comment not resolved; no new envelope compliance calculations have been submitted. [Original comment: Sign and seal the Compliance Statement for the energy conservation code calculations for the building envelope. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.]
11/08/2011 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2011 DELMA ROBEY OUT TO CUSTOMER Completed
11/14/2011 SUE REEVES REJECT SHELF Completed