Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02478
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/19/2011 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Infiniti of Tucson - Expansion T11CM02478 Site Plan (2nd Review) TRANSMITTAL DATE: October 19, 2011 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until the site plan has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\bldg\t11cm02478.doc |
| 10/21/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/02/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/02/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/02/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/02/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. The duct smoke detectors are specified on sheet E0.01 but the note on that sheet says that the duct smoke detector locations are "shown on mechanical plans." [Original comment: Show the locations for the smoke detectors in the return air ducts of heat pumps HP-3 and HP-4, upstream of any outside air connections. Reference: Section 606.1, IMC 2006.] 2. Comment not resolved; no new envelope compliance calculations have been submitted. [Original comment: Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. The building appears to have doors and three different wall types that are not included in the calculations, the roof is not shown as having any cavity-insulation, and the three window types that are included in the calculations are not identified on the drawings. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.] 3. Comment not resolved; no new envelope compliance calculations have been submitted. [Original comment: Sign and seal the Compliance Statement for the energy conservation code calculations for the building envelope. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.] |
| 11/08/2011 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/14/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 11/14/2011 | SUE REEVES | REJECT SHELF | Completed |