Permit Number: T11CM02470
Parcel: 13602002N

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02470
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Show electrical items to be installed on new fire wall.
Ray T Majuta
Electrical Pln Ck
8/8/11
08/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/08/2011 ROBERT SHERRY WATER REVIEW Approved
08/08/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
08/09/2011 DAVE MANN FIRE REVIEW Approv-Cond One room's use is not designated on plan. This room can not be used as a classroom (no exit directly to outside, no sprinklers)
08/09/2011 ERIC NEWCOMB ADA REVIEW Passed
08/09/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/09/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/10/2011 PAUL MACHADO ENGINEERING REVIEW Approved
08/10/2011 STEVE SHIELDS ZONING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2011 DELMA ROBEY OUT TO CUSTOMER Completed