Review Details: COMMERCIAL - TI

Permit Number - T11CM02466
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2011 STEVE SHIELDS ZONING REVIEW Approved
08/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the controls for the restroom fans so they will exhaust all air supplied to the restrooms.
08/08/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/08/2011 ROBERT SHERRY WATER REVIEW Approved
08/08/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/08/2011 PAUL MACHADO ENGINEERING REVIEW Approved
08/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide scald protection for the lavatories (i.e. limit the water temperature to 110 degrees Fahrenheit).
08/08/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

New exit signs on Architectural Plans were not picked up on Electrical.
08/08/2011 RONALD BROWN ADA REVIEW Passed
08/08/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/09/2011 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2011 DELMA ROBEY OUT TO CUSTOMER Completed