Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2011 STEVE SHIELDS ZONING REVIEW Approved
08/05/2011 ELEIBOL1 ENGINEERING REVIEW Approved
08/05/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the control mechanism for the "VAV damper" on the outside air ducts.
2. Provide the gas input and the SEER for the A/C units.
3. Provide specifications for the proposed range in the break room.
4. Revise the control for the restroom exhaust so the fan operates whenever HVAC air is supplied to the restroom.
08/08/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/08/2011 ROBERT SHERRY WATER REVIEW Approved
08/08/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

New exit signs on Architectural Plans were not picked up on Electrical.
08/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide scald prevention for the lavatories (i.e. limit the water temperature to 110 degrees Fahrenheit).
08/09/2011 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2011 DELMA ROBEY OUT TO CUSTOMER Completed