Review Details: COMMERCIAL - TI
Permit Number - T11CM02460
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/05/2011 | ELEIBOL1 | ENGINEERING | REVIEW | Approved | |
08/05/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/08/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the control mechanism for the "VAV damper" on the outside air ducts. 2. Provide the gas input and the SEER for the A/C units. 3. Provide specifications for the proposed range in the break room. 4. Revise the control for the restroom exhaust so the fan operates whenever HVAC air is supplied to the restroom. |
08/08/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
08/08/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/08/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: New exit signs on Architectural Plans were not picked up on Electrical. |
08/08/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide scald prevention for the lavatories (i.e. limit the water temperature to 110 degrees Fahrenheit). |
08/09/2011 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/09/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |