Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2011 DAVE MANN FIRE REVIEW Approved
08/04/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
08/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/04/2011 LHANLY1 WATER REVIEW Approved
08/04/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2.0; FLOOR PLAN: THE SECTION CUT 10/A3.0 AT THE ACCESSIBLE RAMP IS NOT CORRECT. REVISE.
2. SHEET A2.0; FLOOR PLAN: THE ENLARGED PLAN CALL-OUT 5/A3.0 AT THE LOADING RAMP IS NOT CORRECT. REVISE.
3. SHEET A2.0; FLOOR PLAN: THE SECTION CUT 10/A3.0 AT THE LOADING RAMP IS NOT CORRECT. REVISE.
4. SHEET A2.0; FLOOR PLAN: THE NEW OFFICE WALLS ARE NOTED AS "A", BUT NO WALL SCHEDULE WAS LOCATED. PROVIDE OR LIST STUD SIZE AND SPACING.
5. SHEET S1; FOUNDATION PLAN NOTES: NOTE 4 IS NOT INDICATED ON THE PLAN.
6. SHEET MP1.0; M & P PLAN: A NEW 650 LB.HEAT PUMP HAS BEEN ADDED TO THE ROOF. PROVIDE STRUCTURAL CALCULATIONS INDICATING THE EXISTING ROOF CAN SAFELY SUPPORT THIS NEW LOAD.
7. GENERAL: THE TOP OF THE NEW PARTITION WALLS MUST BE BRACED TO RESIST A HORIZONTAL LOAD AS NOTED IN THE IBC, SECTION 1607.13. PROVIDE DETAILS.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/04/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approved
08/04/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/04/2011 ERIC NEWCOMB ADA REVIEW Passed
08/05/2011 STEVE SHIELDS ZONING REVIEW Approved
08/08/2011 JASON GREEN ENGINEERING REVIEW Approved
08/10/2011 GERRY KOZIOL WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2011 DELMA ROBEY OUT TO CUSTOMER Completed