Permit Number: T11CM02419
Parcel: 10309073A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02419
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide structural calculations and details for mounting of heat pump on roof and air handeling unit on interior framing.
2. On detail C4/A4.3, add new door to door schedule and include panic hardware.
08/02/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/02/2011 RONALD BROWN ADA REVIEW Passed
08/02/2011 ROBERT SHERRY WATER REVIEW Approved
08/02/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/02/2011 JASON GREEN ENGINEERING REVIEW Approved
08/02/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/03/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
08/03/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/03/2011 DAVE MANN FIRE REVIEW Approved
08/04/2011 GBONILL1 WWM REVIEW Needs Review