Permit Number: T11CM02418
Parcel: 10824011A

Address:
2450 E RIVER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02418
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2011 TERRY STEVENS ZONING REVIEW Denied Devlopment plan (D11-0023) must be completed and approved prior to approval of the tenant improvement.
08/04/2011 JASON GREEN ENGINEERING REVIEW Denied August 4, 2011

The TI application has been reviewed and approved by the Engineering Section. The TI building plan is denied until further information is provided for review purpose.

- Provide the last approved site plan showing the location of the TI improvment in plan view. If the TI is for the existing building the TI can be approved over the counter with the last approved site plan.

-If the TI improvement is for the new building expansion under the new Development Plan D11-0023 then the TI will be approved once the DP Package is approved through CDRC.

-Clearly show where this improvement is going on an approved site plan.

Jason Green, CFM
08/05/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Passed SEE ACTIVITY T11CM02309 FOR M,P,E IN THIS VAULT
08/08/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Passed SEE ACTIVITY T11CM02309 FOR M,P,E IN THIS VAULT
08/08/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied Structural engineered component ok for foundation, walls, roof beams and LINAC duct.

General notes indicate that there are drawings from Veritas which have not been included in this plan set, please provide those drawings as they may resolve the following 3 corrections.

1) Please clarify attachment methods of shielding components at roof and walls (lead, Verishield blocks)

2) Please clarify how duct penetrations for supply and return air are to be made into this vault. Detail any specialized system shielding.

3) Detail any other penetrations such as for electrical and plumbing that may require specialized treatment.
08/08/2011 LHANLY1 WATER REVIEW Passed SEE ACTIVITY T11CM02309 FOR M,P,E IN THIS VAULT
08/08/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed SEE ACTIVITY T11CM02309 FOR M,P,E IN THIS VAULT
08/08/2011 LHANLY1 WWM REVIEW Passed SEE ACTIVITY T11CM02309 FOR M,P,E IN THIS VAULT

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
08/17/2011 SUE REEVES REJECT SHELF Completed