Permit Number: T11CM02395
Parcel: 117050210

Address:
425 E 7TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02395
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2011 GERRY KOZIOL WWM REVIEW Approved
10/31/2011 DAVID RIVERA ZONING REVIEW Approved
11/02/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/02/2011 ROBERT SHERRY WATER REVIEW Approved
11/02/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The rim elevation of the next upstream sanitary manhole/cleanout (2391') is higher than the first floor elevation (2389.36'). Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson. See also Section 904.1, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2011 DELMA ROBEY OUT TO CUSTOMER Completed
11/04/2011 SUE REEVES REJECT SHELF Completed