Permit Number - T11CM02395
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/28/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/31/2011 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/02/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/02/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/02/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The rim elevation of the next upstream sanitary manhole/cleanout (2391') is higher than the first floor elevation (2389.36'). Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson. See also Section 904.1, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/04/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 11/04/2011 | SUE REEVES | REJECT SHELF | Completed |