Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02395
Parcel: 117050210

Address:
425 E 7TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02395
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2011 MARTIN BROWN FIRE REVIEW Approved
09/29/2011 RONALD BROWN ADA REVIEW Passed
10/04/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond 1. Need to submit special inspection certifications for approval
2. Kitchen Exhaust Hood Number 2 has been removed from the project. It also needs to be deleted from the structural calculations
10/04/2011 DAVID RIVERA ZONING REVIEW Denied Zoning has reviewed the building plans for compliance with the site plan. While zoning acknowledges the building plan for the expansion is in substantial compliance with the site plan the building cannot be approved at this time. The building plans must be approved by the PDSD Commercial Plans reviewers first.

Also, there appears to be an additional site plan attached to the building plans. It is suggested that the approved site plan be attached and incorporated with the building plan set.

Zoning will review the building plans on the next submittal and if applicable approve the plans if the commercial plans reviewers approve the overall building plans. Zoning is willing to review and approve the building plans over the counter when the commercial plans reviewers have approved and stamped the building plans.
10/04/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed None required as per interpretation from Jim Vogelsberg.
10/05/2011 PAUL MACHADO ENGINEERING REVIEW Approved
10/17/2011 ROBERT SHERRY WATER REVIEW Denied 1. The site plan shows one water meter serving this building but the water demand shown on sheet P2 only considers the plumbing fixtures associated with part of the building. Determine the total demand that will be supported by the water meter and provide a letter from Tucson Water confirming that the use of a 5/8" water meter (Tucson Water has not used ¾" water meters in the past) will be allowed for this project.
2. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
10/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate how the termination of the roof drain located in the northeast corner of the existing 1-story building will be affected by the installation of the new walk-in cooler. Reference: Section 103.2.3, UPC 2006.
2. Revise the drainage fixture units used to determine the size of the gravity grease interceptor using the values in Table 7-3; include all of the fixtures draining to the grease waste system (do not include separate fixture units for the floor sinks, just for the fixtures draining into the floor sinks). Reference: Section 1014.3.6, UPC 2006.
3. Provide a specification for the gravity grease interceptor, including the size of the interceptor. Reference: Sections 103.2.3 and 1014.3, UPC 2006.
10/18/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the tag numbers of the exhaust fans. EF-4 is shown on the mechanical floor plan and on the architectural roof plan, but is not scheduled; EF-3 is on the architectural roof plan and scheduled but not shown on the mechanical floor plan. Reference: Section 106.3.1, IMC 2006.
2. Clarify where detail 109 occurs. Reference: Section 106.3.1, IMC 2006.
10/19/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/25/2011 GERRY KOZIOL WWM REVIEW Denied NEED WW/IWC REVIEW & APPROVAL OF GREASE INTERCEPTOR- TOM TOMCHAK- 443-6200 - 5025 W INA RD

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2011 CPIERCE1 OUT TO CUSTOMER Completed
10/27/2011 SUE REEVES REJECT SHELF Completed