Permit Number: T11CM02367
Parcel: 12810078C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02367
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/24/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/24/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise detail 03/P3.1 to comply with the requirements of the 2006 Uniform Plumbing Code. The minimum size for a waste line serving a sink is 2"; the detail appears to show two traps sharing a single trap arm. An indirect waste receptor may not be located within a cabinet. Reference: Sections 704.2, 707.4, 801.2, 804.0, 908.0, and 1001.1, and footnote 2, Table 7-5, UPC 2006. [Previous comment: Comment not resolved; the drain for an ice maker requires an indirect waste to a receptor using an air gap. Show how this will be accomplished. Reference: Section 801.2, UPC 2006.] [Original comment: Clarify and provide a design for the plumbing described in keynote 15, sheet A3.1, "Provide water supply and compensate drain connection through millwork." Reference: Section 103.2.3, UPC 2006.]

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2011 DELMA ROBEY OUT TO CUSTOMER Completed