Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02367
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/24/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/24/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise detail 03/P3.1 to comply with the requirements of the 2006 Uniform Plumbing Code. The minimum size for a waste line serving a sink is 2"; the detail appears to show two traps sharing a single trap arm. An indirect waste receptor may not be located within a cabinet. Reference: Sections 704.2, 707.4, 801.2, 804.0, 908.0, and 1001.1, and footnote 2, Table 7-5, UPC 2006. [Previous comment: Comment not resolved; the drain for an ice maker requires an indirect waste to a receptor using an air gap. Show how this will be accomplished. Reference: Section 801.2, UPC 2006.] [Original comment: Clarify and provide a design for the plumbing described in keynote 15, sheet A3.1, "Provide water supply and compensate drain connection through millwork." Reference: Section 103.2.3, UPC 2006.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/25/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |