Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2011 GERRY KOZIOL WWM REVIEW Approved
08/03/2011 DAVE MANN FIRE REVIEW Approved
08/05/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02367
5431 E Williams BL #101
TI Office

The electrical plans have been denied for the following:
1. The electrical plans are to be sealed by an EE.
2. Sheet E3.1, shows motors to be relocated and re-fed,show panel and circuit numbers.
3. Sheet E3.2. indicate panel and circuit numbers for fixtures, drastic relocation.
4. Sheet E6.1, where is Panel EPP1 located and what effect will it have on existing load , (feeds new pnl DP-VDC), show conductors and conduit sizes.
5. Sheet IT E1.2, indicate what circuit the lights are to be added to and if circuit is sufficient for total load.

Ray T Majuta , Elect Pln CK
PDSD, City of Tucson,
8/8/11,
ray.majuta@tucsonaz.gov
08/15/2011 ROBERT SHERRY WATER REVIEW Approved
08/15/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify and provide a design for the plumbing described in keynote 15, sheet A3.1, "Provide water supply and compensate drain connection through millwork." Reference: Section 103.2.3, UPC 2006.
2. Include sheet P3.1 in the drawing index on sheet A1.1.
3. Section 814.3, UPC 2006 allows air conditioning condensate drains to connect to the tailpiece of plumbing fixtures but detail 03/P3.1 shows the condensate connecting to the waste pipe downstream of an un-vented trap for a sink (and the note on sheet IT-M4.1 is similarly incorrect). Correct the detail to show a code-compliant installation.
4. Show how a vent is to be provided to the sink described in keynote 1, sheet P3.1. Reference: Section 901.1, UPC 2006.
5. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
08/15/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond There exist several architectural type of drawings under the IT drawing reference title that have no registrant seal and signature. Please provide an Arizona registrant seal and signature on all drawings prior to permit issue.
08/15/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. The transfer duct (from room 111 to 112) penetrates a rate fire partition and cannot be equipped with a motorized damper. If control of the air flow in the duct is desired, a combination fire/smoke damper is required; provide a control design and sequence of operation for the fire/smoke damper that includes operation during a smoke or fire event. The fire/smoke damper shall be listed for use in a dynamic system. Reference: Sections 106.3.1, 607.2, 607.3, and 607.3.2.1, IMC 2006.
3. Clarify how room 111 is to be balanced. Approximately 1,000 CFM of hot exhaust air from the condenser coil of CRAC-1 (in room 112) is introduced into the room along with 225 CFM from the VAV system but there is no return grille in the room. Reference: Section 403.1, IMC 2006.