Permit Number: T11CM02365
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02365
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2011 DAVID RIVERA ZONING REVIEW Approved
07/28/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted (e.g. evenif. Reference: Section 403.2.1 (4), IMC 2006
07/28/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/28/2011 ROBERT SHERRY WATER REVIEW Approved
07/28/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A9; ELEVATION 3 (EXTERIOR TOILET ROOM): A DETAIL REFERENCES 11/A9 FOR A CAP. THIS IS INCORRECT. REVISE.
2. THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. SEVERAL LOCATIONS ON THE PLANS DO NOT MEET THIS REQUIREMENT. REVISE.
3. SHEET A8; WALL BRACING: PROVIDE BRACING DETAILS FOR PARTITION WALLS THAT ARE NOT FULL HEIGHT (SEE WALL SCHEDULE ON A1.2 FOR LOCATION).
07/28/2011 GERRY KOZIOL WWM REVIEW Approved
07/28/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the hot water for the lavatories will be limited to a maximum temperature of 110 degrees Fahrenheit.
2. Provide vacuum relief for the storage-type water heater located above the hot water outlets.
07/28/2011 LOREN MAKUS ENGINEERING REVIEW Approved
07/28/2011 MARTIN BROWN FIRE REVIEW Approved
07/28/2011 ERIC NEWCOMB ADA REVIEW Passed
07/28/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2011 DELMA ROBEY OUT TO CUSTOMER Completed