Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02362
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/14/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide a 1 hour fire rated separation wall on the west side of the carport as required by table 602. RESUBMITTAL COMMENT As per table 602, the carport must be 10' minimum from the property line or have a 1 hour wall constructed on the Wets side. 2. Please fill out the required building code check list form and submit with application. RESUBMITTAL COMMENT No building code data was submitted. What is your building type, occupancy classification and etc. Please reference the building code check list form on the P&DSD web site. END OF RESUBMITTAL REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/19/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/19/2011 | SUE REEVES | REJECT SHELF | Completed |