Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T11CM02362
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Provide fire wall at property line per IBC Table 602. Show total new square footage and type of construction. Show distance to nearest fire hydrant. |
| 08/16/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide a 1 hour fire rated separation wall on the west side of the carport as required by table 602. 2. Please fill out the required building code check list form and submit with application. END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/17/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/17/2011 | SUE REEVES | REJECT SHELF | Completed |