Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02343
Parcel: 14029003H

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T11CM02343
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A7.0; KEYNOTES: KEYNOTE 13 ON CLEAN ROOM SECTION 4 IS INCORRECTLY SHOWN. REVISE.
2. SHEET A7.0; KEYNOTES: PROVIDE KEYNOTE 13 ON THE APPROPRIATE SECTION.
3. SHEET A7.0 (CLEAN ROOM SECTION 4); SHEET S2.2 (CEILING FRAMING PLAN): THE ARCHITECTURAL SECTION INDICATES A 1/4"/1' CEILING SLOPE, WHILE THE STRUCTURAL PLAN DOES NOT INDICATE THAT SLOPE. COORDINATE.
4. GENERAL: AN UNVENTED ATTIC SPACE HAS BEEN CREATED BY THE CLEAN ROOM ADDITION. REVISE PER THE 2006 IBC SECTION 1203 AND PROVIDE ACCESS PER THE 2006 IBC..
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL COMMENTS.
12/12/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the sequence of operation for AC-2 and AC-3. A balancing note on detail 1/M1.1 implies that the units may operate either singly or in tandem but the ventilation for the space requires both units to be operating.
2. Coordinate the design of the top of the plenum with the architect. On sheet A7.0 the top of the plenum is pitched at 1/4 per foot down from column G to column J.
12/12/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved