Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM02343
Parcel: 14029003H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02343
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/16/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved; finish labeling the sizes of the condensate drain pipes. Verify the sizing of the condensate drain piping; finish labeling the condensate drain segments on sheet P1.1 (e.g. the section of pipe downstream of AC-23 is under sized). Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson.
2. Comment not resolved; no clean room plans were included in the submitted documents. Provide plans and specifications for the proposed clean room. Reference: Sections 106.3.1, 301.4, and 302.1, IMC 2006.
08/16/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/16/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed. Appliances (e.g. humidifiers, softeners, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.12, and Table 608.1, IPC 2006.
08/22/2011 CAGUILA1 WWM REVIEW Needs Review