Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02343
Parcel: 14029003H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02343
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2011 SREEVES1 ADA REVIEW Passed
07/27/2011 GERRY KOZIOL WWM REVIEW Denied need 5th floor credit evaluation
need addressing review of suite number
07/27/2011 MARTIN BROWN FIRE REVIEW Approved
08/01/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; CODE REVIEW (PLUMBING SYSTEMS): THE ANALYSIS INDICATES 5 DRINKING FOUNTAINS REQUIRED AND 1 PROVIDED. REVISE.
2. SHEET A1.0; CODE REVIEW (PLUMBING SYSTEMS): THE ANALYSIS INDICATES 6 TOILETS AND 3 URINALS ARE PROVIDED. INDICATE HOW MANY OF THE URINALS ARE ACCESSIBLE.
3. SHEET A5.0; PLAN 3: HORIZONTAL AND VERTICAL GRAB BARS ARE REQUIRED IN THE TRANSFER-TYPE SHOWERS PER THE ICC/ANSI A117.1-2003, SECTION 608.3.1. INDICATE ON THE DRAWING.
4. SHEET S1.3; PURLIN SCHEDULE: THERE ARE TWO NOTE 3'S IN THE SCHEDULE. REVISE.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/04/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02343
3400 E Britianna Dr


Submit 2006 IECC Lighting Budget Calculations,Com Check ok.

Ray Majuta
PDSD, City of Tucson
Elect Pln Ck
8/5/11
Ray.majuta@tucsonaz.gov
08/05/2011 ROBERT SHERRY WATER REVIEW Approved
08/05/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Appliances (e.g. humidifiers, softeners, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.12, and Table 608.1, IPC 2006.
08/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the types and quantities of any hazardous materials stored or used in the production areas, labs, clean room, and the stockroom. Reference: Section 414, IBC 2006.
2. Verify the sizing of the condensate drain piping; finish labeling the condensate drain segments on sheet P1.1 (e.g. the section of pipe downstream of AC-23 is under sized). Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson.
3. Provide plans and specifications for the proposed clean room. Reference: Sections 106.3.1, 301.4, and 302.1, IMC 2006.
4. Provide material standards for mechanical equipment being supplied by others but installed as part of this activity. Reference: Sections 106.3.1, 301.4, and 302.1, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
08/15/2011 SUE REEVES REJECT SHELF Completed