Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02343
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/26/2011 | SREEVES1 | ADA | REVIEW | Passed | |
07/27/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | need 5th floor credit evaluation need addressing review of suite number |
07/27/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/01/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0; CODE REVIEW (PLUMBING SYSTEMS): THE ANALYSIS INDICATES 5 DRINKING FOUNTAINS REQUIRED AND 1 PROVIDED. REVISE. 2. SHEET A1.0; CODE REVIEW (PLUMBING SYSTEMS): THE ANALYSIS INDICATES 6 TOILETS AND 3 URINALS ARE PROVIDED. INDICATE HOW MANY OF THE URINALS ARE ACCESSIBLE. 3. SHEET A5.0; PLAN 3: HORIZONTAL AND VERTICAL GRAB BARS ARE REQUIRED IN THE TRANSFER-TYPE SHOWERS PER THE ICC/ANSI A117.1-2003, SECTION 608.3.1. INDICATE ON THE DRAWING. 4. SHEET S1.3; PURLIN SCHEDULE: THERE ARE TWO NOTE 3'S IN THE SCHEDULE. REVISE. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
08/04/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/04/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM02343 3400 E Britianna Dr Submit 2006 IECC Lighting Budget Calculations,Com Check ok. Ray Majuta PDSD, City of Tucson Elect Pln Ck 8/5/11 Ray.majuta@tucsonaz.gov |
08/05/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/05/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Appliances (e.g. humidifiers, softeners, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.12, and Table 608.1, IPC 2006. |
08/08/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the types and quantities of any hazardous materials stored or used in the production areas, labs, clean room, and the stockroom. Reference: Section 414, IBC 2006. 2. Verify the sizing of the condensate drain piping; finish labeling the condensate drain segments on sheet P1.1 (e.g. the section of pipe downstream of AC-23 is under sized). Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson. 3. Provide plans and specifications for the proposed clean room. Reference: Sections 106.3.1, 301.4, and 302.1, IMC 2006. 4. Provide material standards for mechanical equipment being supplied by others but installed as part of this activity. Reference: Sections 106.3.1, 301.4, and 302.1, IMC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/15/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
08/15/2011 | SUE REEVES | REJECT SHELF | Completed |