Permit Number: T11CM02316
Parcel: 13602002N

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02316
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2011 MICHAEL ST. PAUL ZONING REVIEW Passed
07/21/2011 JASON GREEN ENGINEERING REVIEW Approved
07/22/2011 ERIC NEWCOMB ADA REVIEW Passed
07/22/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide sealed drawings.
2. Clarify the installation of HP-11; no duct work is shown.
3. Provide structural calculations for the addition of HP-11.
4. Show the size, route, and termination of the condensate drain for HP-11.
07/22/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/22/2011 ROBERT SHERRY WATER REVIEW Approved
07/22/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/22/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
07/22/2011 MARTIN BROWN FIRE REVIEW Approved
07/22/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/01/2011 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review