Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02316
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
| 07/21/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/22/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 07/22/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide sealed drawings. 2. Clarify the installation of HP-11; no duct work is shown. 3. Provide structural calculations for the addition of HP-11. 4. Show the size, route, and termination of the condensate drain for HP-11. |
| 07/22/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/22/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/22/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/22/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 07/22/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/22/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/01/2011 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |