Permit Number: T11CM02305
Parcel: 10510010D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02305
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2011 STEVE SHIELDS ZONING REVIEW Approved
07/20/2011 JASON GREEN ENGINEERING REVIEW Approved
07/21/2011 ERIC NEWCOMB ADA REVIEW Passed
07/21/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/21/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR THIS PROJECT.
2. SHEET S2.1; FRAMING PLAN NOTES: NOTE 1 INDICATES POST TENSIONED CONCRETE SLAB. IS IT POST TENSIONED OR PRECAST? VERIFY.
3. SHEET S2.1; FRAMING PLAN NOTES: NOTE 3 INDICATES POST TENSIONED CONCRETE BEAM. IS IT POST TENSIONED OR PRECAST? VERIFY.
4. SHEET S3.1; DETAILS: VERIFY ALL REFERENCES TO POST TENSIONED CONCRETE.
5. SHEET S3.1; DETAILS 103 AND 106: A DETAIL NOTE INDICATES TO LOCATE EPOXY BOLTS " 3" MINIMUM CLEAR FROM EXISTING TENDONS". HOW ARE TENDONS LOCATED? VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/21/2011 ROBERT SHERRY WATER REVIEW Approved
07/21/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Relocate the specified backflow prevention valves or provide maintenance access per Section 603.3.4, UPC 2006.
07/21/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/22/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11cm02305
333 Wetmore RD #450


How is the total affected by the addition of these loads ?

R T Majuta
Elect Pln Ck
PDSD City of Tuc
7/22/11
Ray.majuta@tucsonaz.gov
07/27/2011 DROBEY1 WWM REVIEW Needs Review
07/27/2011 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/27/2011 DELMA ROBEY OUT TO CUSTOMER Completed