Permit Number - T11CM02297
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/28/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.7 (SECTION 2); STRUCTURAL CALCULATIONS : THE FOOTING FOR THE NEW FULL HEIGHT WALL SHOWN ON THE PLANS DOES NOT MATCH THE FOOTING INDICATED IN THE CALCULATIONS. REVISE. 2. SHEET A1.7 (SECTION 2); STRUCTURAL CALCULATIONS: THE CALCULATIONS INDICATE THE NEW FULL HEIGHT WALL IS TO BE SOLID GROUTED. INDICATE THAT ON SECTION 2. 3. SHEET A1.7; SECTION 2: ARE THE NEW MASONRY WALL EXTENSIONS OF THE EXISTING WALLS TO BE SOLID GROUTED? VERIFY. |