Permit Number: T11CM02290
Parcel: 12710017D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02290
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2011 STEVE SHIELDS ZONING REVIEW Approved
07/19/2011 JASON GREEN ENGINEERING REVIEW Approved
07/20/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/20/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide justification for the amount of ventilation provided to the therapy room (equal to an office).
07/20/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE SITE PLAN PER CITY OF TUCSON SUBMITTAL REQUIREMENTS.
2. SHEET TS.1; GENERAL NOTES (APPLICABLE CODES): ICC/ANSI IS 2003 EDITION. REVISE.
3. SHEET TS.1; GENERAL NOTES: REMOVE ALL ORO VALLEY AND GOLDER RANCH REFERENCES IN NOTE 10.
4. SHEET TS.1; GENERAL NOTES: REVISE COUNTY IN NOTE 1.
07/20/2011 ROBERT SHERRY WATER REVIEW Approved
07/20/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Note: this review has been done using the 2006 UPC based on note 1 on the General Plumbing Notes.
1. Revise the size of the wet vent serving P-1 and P-3 per Section 908.2, UPC 2006.
2. Vertical wet venting is limited to 1 and 2 fixture unit fixtures; a clothes washer does not qualify for this use. reference: Section 901.1, UPC 2006.
3. Provide a vacuum relief valve for the water heater per Section 608.7, UPC 2006.
07/20/2011 DAVE MANN FIRE REVIEW Approved
07/20/2011 ERIC NEWCOMB ADA REVIEW Passed
07/20/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/25/2011 CPIERCE1 WWM REVIEW Needs Review