Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02288
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM02288 1550 N Country Club #4101 Activity and Learning Center 1. The disconnects for the compressors cannot be located behind the units,they need requirzed clearances per 110.26, 2005 NEC. 2. Water heater requires a disconnect means,please show on plan. 3. Show circuit A-5 to be GFCI protected. 4. On Panel C schedule circuit 18 is spare and circuit 16 is for maint receptacles,should be the other way. 5. Cannot find condensor units on specification sheet provided,(Sheet M-1) also the HPC listed as 14.5 amps max 25 amps (the lower amperage unit) is shown in Panel C as the higher amperage unit. Ray T Majuta, Elect Pln Ck,PDSD, City of Tucson, 7/23/11 Ray.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/25/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 07/25/2011 | SUE REEVES | REJECT SHELF | Completed |