07/25/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02288
1550 N Country Club #4101
Activity and Learning Center

1. The disconnects for the compressors cannot be located behind the units,they need requirzed clearances per 110.26,
2005 NEC.
2. Water heater requires a disconnect means,please show on plan.
3. Show circuit A-5 to be GFCI protected.
4. On Panel C schedule circuit 18 is spare and circuit 16 is for maint receptacles,should be the other way.
5. Cannot find condensor units on specification sheet provided,(Sheet M-1) also the HPC listed as 14.5 amps max 25 amps (the lower amperage unit) is shown in Panel C as the higher amperage unit.


Ray T Majuta,
Elect Pln Ck,PDSD,
City of Tucson,
7/23/11