612 N 7th av
Photovoltaic System


1. The type of ILSCO KUP-L-Tap connectors not approved for this type of tap on line side,condutors on line side taps must be fixed and approved terminals used.
2. The service is a 400 a 120/240 3 phase, indicating a stinger leg. Indicate which legs will be tapped into at line side.
3. The SB 5000US Inverter specification sheet shows a max input current of 21amps, the plan shows 25 amps, also spec sheet shows 5000 Wp, plan shows 4000-6000 Wp,appears the reference is made to the 6000WP verses the 5000Wp ?
4. Indicate on plan size of PV system.

Ray T Majuta
Elect Plan Ck
PDSD,City of Tuc,
7/19/11