Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T11CM02283
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/19/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/19/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/19/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Completed | |
| 07/20/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T11CM02283 612 N 7th av Photovoltaic System 1. The type of ILSCO KUP-L-Tap connectors not approved for this type of tap on line side,condutors on line side taps must be fixed and approved terminals used. 2. The service is a 400 a 120/240 3 phase, indicating a stinger leg. Indicate which legs will be tapped into at line side. 3. The SB 5000US Inverter specification sheet shows a max input current of 21amps, the plan shows 25 amps, also spec sheet shows 5000 Wp, plan shows 4000-6000 Wp,appears the reference is made to the 6000WP verses the 5000Wp ? 4. Indicate on plan size of PV system. Ray T Majuta Elect Plan Ck PDSD,City of Tuc, 7/19/11 Ray.majuta@tucsonaz.gov |