Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02280
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/19/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
07/19/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
07/19/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM02280 2460 N Swan RD TI Retail Electrical plans denied for following: 1. Provide fault current value at Main disconnect and at panel,Utility SR Book shows a FC of 27,800 a at utility transformer. 2. Provide 2006 IECC Light Budget calculations, required per commercial submittals. 3. Lighting circuits for P-1,3,5 and 7 show much lower loads than indicated by number of lights ,va"s,and lampss. 4.See mechcanical plans examiner statements, air input into restrooms must be exhausted per equal volum,how will this be done electrically. Ray T Majuta, Elect Pln Ck,PDSD, City of Tucson. 7/19/11 Ray.majuta@tucsonaz.gov |
07/19/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/19/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/19/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
07/19/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
07/19/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
07/19/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/16/2011 | DROBEY1 | WWM | REVIEW | Needs Review | |
08/16/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/16/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |