Permit Number: T11CM02252
Parcel: 108201360

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM02252
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:

" Limit all code references to those recognized by the City of Tucson. Show the 2006 code reference at note #16, sheet A2.

FLOOR PLANS:

1. Show the door from a garage to dwelling with a self-latching provision, 2006 IRC Amendment section 309.1.

STRUCTURAL PLANS:

1. Provide window and door header sizes consistent with Table 502.5(1) & (2).
2. Provide a complete braced panel layout, Table R602.10.5. The new garage wall is a required braced interior wall line at 35' from the back exterior wall line, R602.10.1.1.

SECTIONS - DETAILS:

1. Show a minimum ½" diameter anchors or expansion bolts at new garage wall sill plate, R319.1 & R403.1.6. Ram set pins are not appropriate for braced walls.
2. Show bracing and fastening detail of garage braced wall panels to ceiling joist or roof rafters, R602.10.
3. Show the full beam depth with minimum 1-1/2" bearing contact to supporting members, R502.6. Revise detail S4/A2.
4. Show a post/beam fastener with appropriate uplift capacity, R802.11. Revise detail S4/A2.
5. Show the porch roof sheathing method of installation, R905. Edge and mid-point perpendicular fastening not greater than 48" OC.

PLUMBING PLANS:

1. Provide a gas (1,000 BTUh = 1 CFH) conversion coordinated with Southwest Gas.
2. Provide gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Show a 1-1/2" supply to the first branch tee; a 1-1/4" line between the furnace branch tee & the range tee and a 1" branch to the WH#2/dryer tee.

MECHANICAL PLANS:

1. Identify the evaporative cooler duct point of connection to existing duct or show new air register sizes, M1302.1.

ELECTRICAL PLANS:

1. Revise the description of the load calculation from "NEW" SUB PANEL "B" to LOAD CALCULATION.
2. Provide a sub-panel clear working space of 30"wide x 36"deep, E3305.2.
3. Provide an appropriate feeder conductor size for the 60 AMP sub panel, E3502.1 & E3605.1.
4. Show a receptacle outlet in the garage with ground fault circuit interrupting protection. Label each receptacle GFCI requiring such protection and show the circuit number on the plan, E3802.
5. Show at least one wall switch controlled light in attached garages, E3803.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Show the "R" values of ceiling insulation and the maximum "U" factors of the windows and doors on the plans, N1101.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review