Permit Number: T11CM02251
Parcel: 117160030

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02251
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied A3 occupancy is not fully sprinklered as shown on plans. You may go to separated use and delete references to the gallery areas for approval of this plan.
09/01/2011 MARTIN BROWN FIRE REVIEW Denied Provide fire sprinklers in east portion of building or separate per 2006 IBC.
09/01/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approved
09/01/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/08/2011 GERRY KOZIOL WWM REVIEW Denied need to review location/method of connection to public sewer