Review Details: COMMERCIAL - TI
Permit Number - T11CM02251
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/01/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | A3 occupancy is not fully sprinklered as shown on plans. You may go to separated use and delete references to the gallery areas for approval of this plan. |
09/01/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Provide fire sprinklers in east portion of building or separate per 2006 IBC. |
09/01/2011 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
09/01/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/08/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | need to review location/method of connection to public sewer |