Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM02251
Parcel: 117160030

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02251
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PP A1.O
a) REFERNCE TO ANSI 117.1 SHOULD INDICATE 2003 EDITION
b) DELETE REFERENCE TO 1991 ADAAG
c) TYPE OF CONSTRUCTION IS III-B
d) PROVIDE CORRECT CALCULATIONS FOR ALLOWABLE AREA. ALLOWABLE AREA BEGINS AT 9500 SQUARE FEET FOR ADJACENT GALLERY, OR YOU NEED TO PROVIDE A FIRE WALL BETWEEN TENANTS
e) BUILDING SUMMARY AREAS INCORRECT
f) COMPELTE ALLOWABLE AREA CALCULATIONS FOR ENTIRE BUILDING OR PROVIDE FOR SEPARATED USE WITH A FIRE-WALL.

PP A1.
a) THERE ARE REFERENCES TO EXISTING STAIRS, GUARDRAILS, ETC THAT ARE ACTUALLY NEW WORK THAT WAS DONE WITHOUT PERMITS. PLEASE NOTE THAT ALL SITE IMPROVEMENTS MUST BE MADE TO COMPLY WITH CURRENT ADOPTED CODES.
b) PROVIDE AN ACCESSIBLE ROUTE FROM 7TH AVE OR JUSTIFY WHY IT HASN'T BEEN PROVIDED.
c) JUSTIFY "EXISTING PARKING" NOTATION. TDOT HAS BLOCKED ACCESS TO THAT AREA FROM 7TH.
d) CLARIFY KEYNOTE 12 AT WEST SIDE OF BUILDING.

PP A3.O
a) JUSTIFY ALL "EXISTING" WALLS, DOORS, WORKTABLES, ETC. THIS BUILDING HAD NO SUCH WORK DONE UNDER THE REQUIRED BUILDING PERMITS.
b) OCCUPANT LOADS CALCULATED INCORRECTLY

PP A3.1 TRAVEL DISTANCE CALCULATED INCORRECTLY

PP A5.1
a) DIMENSION PLACEMENT OF ALL GRAB-BARS, LAVS, WATER CLOSETS, ETC. OR PROVIDE CUT REFERENCE TO DETAIL SHEETS
b) CLARIFY ALL "TA-" REFERENCE TAGS

PP A9.0 DETAILS 4 & 5 NEED TO ACCURATELY REFLECT ACTUAL LAYOUT OF RESTROOM, NOT A GENERIC MODEL. REFERENCE IN 4 TO 'ADA' IS INACCURATE AND SHOULD BE DELETED OR MODIFIED TO REFLECT ANSI 117.1 SECTION 606.6
07/19/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/19/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PLANS INDICATE EXISTING 600 A 3-PHASE SERVICE WITH 4 EXISTING PANELS, 1 NEW PANEL AND 1 FUTURE PANEL. SITE ONLY HAS A 200 A SERVICE WITH 1 SUBPANEL (NOTED AS "A" ON PLANS) AND SOME FLOURESCENT LIGHTING.

REVIEW STOPPED DUE TO INABLITY TO ACCURATELY EVALUATE NON-EXISTING EQUIPMENT NOTED AS EXISTING.

FOR NEXT REVIEW PROVIDE:
1) COMPLETE SET OF PLANS FOR ALL WORK TO BE DONE
2) OUTDOOR LIGHTING CODE COMPLIANCE INFORMATION

PROVIDE IECC LIGHTING COMPLIANCE CERTIFICATE FOR NEXT REVIEW
07/19/2011 ROBERT SHERRY WATER REVIEW Approved
07/20/2011 STEVE SHIELDS ZONING REVIEW Approved
07/20/2011 JASON GREEN ENGINEERING REVIEW Approved
07/20/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

1. Interior and exterior stairs and railings were installed without permits. Show complete compliance with IFC Chapter 10.

2. The occupancy has an M componant added. Show new occupant load calculations. Occpant load is shown as both 29.4 and 59.4. If this is an F2 a fire separation will be required to the A3 occupancy next door. Provide new area calculations for the new occupancies. The information on this sheet shows an increase for sprinklers. This is only allowable if the building is fully sprinklered.
07/27/2011 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to include the following information:
a the location and size of the water meter
b.the location of the main water lines and fire hydrants
c.The location of the gas meter
d.the location and size of the public sanitary sewer and
e.the location, invert, and rim elevation of all manholes and cleanouts.
Reference: City of Tucson Development Standard No. 2-01.1.0 2 3.8 D and Section 103.2.3, UPC 2006.
2. reference 304 2006 upc. connections to plumbing system required. only fixtures listed in chapter eight may be indirectly wasted. hand sinks to be directly connected to sanitary drain. three and four compartment sinks are to be directly connected to sanitary sewer unless one bowl is used for vegetable prep, or used as a sanitizing bowl, then that bowl is to be indirectly wasted. 3. provide the existing roof drains and overflow drains for reference. show where and how they terminate.
08/16/2011 CAGUILA1 WWM REVIEW Needs Review