Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM02152
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02152
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Exit cannot go through rear kitchen.

Defered submittal will be required on hood system.

Panic hardware required on rear door.

Remove alarm system note or put in alarm.
07/21/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide accessible seating as required by the 2006 IBC, Section 1109.11.
2. At Detail y/A3.1:
a. Because project is a change of use all elements must meet current 2006 IBC.
b. Please show all accessible requirements on existing toilet room elevations and floor plan.
c. This includes all dimensions, accessories, clearances, toilet fixtures and signage.
3. Please confirm hardware on existing toilet room doors and clarify maneuvering clearances as per Section 404.2.3.1.
4. Run the dining room floor finish to the east edge of the east Janitor closet wall and label this area as Vestibule, 111.
5. Detail 1A/A2.1: Call out the size of the braces.
6. Detail a/A4.1: Where does B.O. DECK change to A.F.F. 8'-0"? Please show on ceiling plan.
END OF REVIEW
07/26/2011 GERRY KOZIOL WWM REVIEW Denied NEED 5TH FLOOR CREDIT EVALUATION
08/04/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006.
2. Provide structural calculations and details to show that the Type I hoods are supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
3. Provide a grease drain and collection reservoir at the lowest point of the fan housing (i.e. at the bottom of the scroll). Reference: Section 506.5.2, IMC 2006.
4. Verify that the presence of 4-way air diffusers located within two feet of the hoods will not adversely affect the capture and containment performance of the hoods. Reference: Section 507.16.1, IMC 2006.
5. Clarify the air flow to the supply plenums for the two Type I hoods; the kitchen hood schedule shows 625 CFM being supplied to each hood but the mechanical plan implies otherwise. Reference: Section 508.1, IMC 2006.
08/04/2011 ROBERT SHERRY WATER REVIEW Denied Provide sufficient information (e.g. water meter size and total connected water demand) to show that the installation of the new plumbing fixtures will not cause the existing water supply system to become overloaded. Reference: Section 101.5.1, UPC 2006.
08/05/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanouts for the horizontal drains serving P-3 and the P-2 serving the dishwasher. Reference: Section 708.3.1, IPC 2006.
2. Show how adequate combustion air is being provided for the gas-fired water heater. Reference: Section 304.1, IFGC 2006.
08/08/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved