Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02131
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. At details 16 and 17 on sheet A-2.1 the sill detail reflects a manufactures spec of model numbers AS-86 or AS-88 as per submitted manufactures cut sheets. The head detail and structural support shown in detail 17 does not match either corresponding manufacturer's cut sheet head details and required structural support. Please provide a structural detail and calculations that will support the head of the curtain wall as required by manufacturer. 2. The men's toilet stall dimensions needs to show a 1" thick partition wall to maintain an accessible toilet stall clear width of 5'-0" and an ambulatory stall clear width of 3'-0". END OF REVIEW |
| 09/28/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/28/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the piping configuration of the water heater detail on sheet P0.1 to show the hot water return piping routed to the cold water inlet pipe of the water heater, terminating between the shut off valve and the check valve on the cold water inlet. [Original comment: Revise the piping configuration of the water heater detail on sheet P0.1 to show the hot water return piping routed to the cold water inlet pipe of the water heater. Reference: Section 607.2.3, IPC 2006.] 2. Provide structural calculations for the water heater shelf design shown on sheet P0.1. [Original comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Section 307.1, IPC 2006.] 3. Revise the water heater detail to show the vacuum relief valve located per the manufacturer's listing; between the water heater and any valves on the cold water inlet. [Original comment: Show how the specified water heater, WH-1, complies with the requirements of Section 504, IPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/03/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |