Permit Number: T11CM02124
Parcel: 133148280

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02124
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET a2.0: NOTES 6 AND 11 INDICATE NEW INTERIOR PARTITIONS. PER THE 2006 IBC SECTION 1607.13, INTERIOR PARTITIONS THAT EXCEED 6' IN HEIGHT MUST HAVE ADEQUATE STRENGTH TO RESIST A HORIZONTAL LOAD OF 5 PSF. PROVIDE DETAIL(S) INDICATING BRACING AT THE TOP OF THE WALLS, INCLUDING BRACING SIZE AND SPACING, AND CONNECTIONS TO THE TOP OF THE PARTITION WALL AND TO THE STRUCTURE ABOVE.
07/07/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/07/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
07/07/2011 ROBERT SHERRY WATER REVIEW Approved
07/07/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/07/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
07/07/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/07/2011 JASON GREEN ENGINEERING REVIEW Approved
07/07/2011 ERIC NEWCOMB ADA REVIEW Passed
07/20/2011 CPIERCE1 ZONING REVIEW Needs Review
07/20/2011 CPIERCE1 FIRE REVIEW Needs Review