Permit Number: T11CM02109
Parcel: 105110690

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T11CM02109
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved 1. Need riser diagram to be correct, does not match picture in drawing.
2. New panel D is not in floor plan , no location is given for it?
3. The new circuits in panel D are not in the floor plan ?


Ray T Majuta
Elect plan Ck
11/22/11

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2011 CPIERCE1 OUT TO CUSTOMER Completed