Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T11CM02109
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/22/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1. Need riser diagram to be correct, does not match picture in drawing. 2. New panel D is not in floor plan , no location is given for it? 3. The new circuits in panel D are not in the floor plan ? Ray T Majuta Elect plan Ck 11/22/11 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/29/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |