Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM02109
Parcel: 105110690

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02109
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/22/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/23/2011 GERRY KOZIOL WWM REVIEW Denied NEED PLUMBING DRAWINGS TO AGREE, PLAN, ISOMETRICS, ETC
09/26/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the waste and vent piping as shown on sheets P1.0 and P4.0.
09/26/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02109,
4386 N Oracle Rd

Item # 2 from previous review remains unclear , your last
response indicated an existing 1200 amp rated service with this TI taking 454 amps thus 746 amps remaining. This is insufficient, provide the actual size of service available in amperage, then indicate the ampacity of other units using power, ( possibly two ) add them to this TI'S total and provide sum.
Item # 7 on last review, provide a detail of what the switching will be ( how many Dimmers) and for which lights they will controll. Will this be individual dimmers for each circuit?

Ray T Majuta,
Elect Pln Review,
PDSD, City of Tucson,
9/26/11
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2011 DELMA ROBEY OUT TO CUSTOMER Completed