Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02109
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/20/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/22/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/23/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED PLUMBING DRAWINGS TO AGREE, PLAN, ISOMETRICS, ETC |
09/26/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Coordinate the waste and vent piping as shown on sheets P1.0 and P4.0. |
09/26/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM02109, 4386 N Oracle Rd Item # 2 from previous review remains unclear , your last response indicated an existing 1200 amp rated service with this TI taking 454 amps thus 746 amps remaining. This is insufficient, provide the actual size of service available in amperage, then indicate the ampacity of other units using power, ( possibly two ) add them to this TI'S total and provide sum. Item # 7 on last review, provide a detail of what the switching will be ( how many Dimmers) and for which lights they will controll. Will this be individual dimmers for each circuit? Ray T Majuta, Elect Pln Review, PDSD, City of Tucson, 9/26/11 Ray.majuta@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/27/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |